Refrigerant charge — superheat or subcooling, not a guess
ENERGY STAR's contractor checklist includes checking the refrigerant level and adjusting if necessary, noting that too much or too little refrigerant makes the system less efficient and shortens equipment life. The way that check is done matters.
Charge is verified by measurement against the manufacturer's charging data. Systems with a thermostatic expansion valve (TXV) or electronic expansion valve are typically charged by subcooling; systems with a fixed metering device are typically charged by superheat, using indoor and outdoor conditions to find the target. The technician connects gauges or digital probes, takes line temperatures, and compares the result to the chart. 'The pressures look about right' is not a charge check.
Temperature split across the indoor coil
The temperature difference between return air entering the indoor coil and supply air leaving it is a quick health indicator. A split that's well below normal can point to low charge, a dirty coil, or excessive airflow; a split that's unusually high can point to low airflow from a dirty filter, restricted ducts, or a blower problem.
The split is interpreted against indoor humidity — humid air spends more of the coil's capacity on removing moisture, so the dry-bulb drop is smaller. That's why the split is a screening measurement, not a substitute for a proper charge check.
Electrical — amp draw, capacitors, contactors
ENERGY STAR lists tightening electrical connections and measuring voltage and current on motors as standard check-up items, noting that faulty connections can make the system operate unsafely and shorten component life. On an AC that translates to a short list of metered checks:
- Compressor and condenser fan amp draw compared to the nameplate ratings — high draw flags a struggling motor or compressor
- Run capacitor tested in microfarads (µF) against the value and tolerance printed on its label — a weak capacitor is one of the most common summer failures
- Contactor contacts inspected for pitting or burning — pitted contacts cause chattering, voltage drop, and eventual failure to start
- Supply voltage at the disconnect and wiring terminations checked and tightened
- Blower motor amp draw and, where applicable, blower capacitor tested
Coils, airflow, and the condensate drain
ENERGY STAR calls for cleaning the evaporator and condenser coils, noting that dirty coils reduce the system's ability to cool and make it run longer. In the Sacramento region the outdoor coil takes most of the abuse — dust, pollen, cottonwood fluff, grass clippings — and a fouled condenser raises head pressure and compressor temperature on every hot afternoon.
The indoor side gets an inspection of the coil face where accessible, blower wheel cleanliness, and filter condition. The condensate system gets cleared and tested: the drain line, the trap, and any float or overflow safety switch that shuts the system off before a clogged drain floods a ceiling.
Controls and the start-up cycle
The last part of the visit confirms the system starts, runs, and shuts off properly — ENERGY STAR lists checking the starting cycle and the controls as their own items. That includes thermostat settings and calibration, a full call-for-cooling cycle observed from start to stop, and any staging or variable-speed behavior on equipment that has it.
How to recognize a look-and-leave visit
A maintenance visit that doesn't connect any instruments can't verify charge, capacitor health, or motor condition. A few questions sort a measured tune-up from a cursory one:
- Did the technician connect gauges or temperature probes to the refrigerant lines?
- Can they tell you the superheat or subcooling reading and the target it was compared to?
- Were capacitor values recorded, not just 'looked okay'?
- Was the outdoor coil cleaned, and the condensate drain cleared and tested?
- Did you receive a written summary of what was inspected and found?
Common questions
How long should an AC tune-up take?
Long enough to take the measurements and clean what needs cleaning. Coil condition, access to the indoor unit, and what's found all change the time. A visit that's over in a few minutes almost certainly skipped the measured checks.
Should a technician add refrigerant during a tune-up?
Only if measurement shows the charge is low — and if it's low, refrigerant leaked out somewhere, because it doesn't get consumed. A repeated top-off without finding the leak isn't a fix; our refrigerant leak article covers the fix-versus-replace decision.
What is a capacitor and why does it fail in summer?
A run capacitor stores and releases electrical energy to help the compressor and fan motors start and run efficiently. Heat accelerates its degradation, so capacitors in hot outdoor units lose capacitance over time. Testing it against its rated microfarad value catches a weak one before it fails to start the compressor on a hot afternoon.
Is a heat pump tune-up the same as an AC tune-up?
The cooling-mode checks are the same. A heat pump also needs its reversing valve and defrost operation verified, and any backup heat strips tested — checks that have no equivalent on a straight air conditioner.
Reviewed and published by Statewide HVAC